Vlc 1600 Datasheet Official

The VLC-1600 is primarily used in central plant systems and lighting panels where high input density is required to monitor multiple process variables simultaneously. It is often paired with other controllers like the VLC-16160-E, which provides the binary outputs the 1600 lacks. hbt-bms-VLC-1600-E-datasheet.pdf

: Fully programmable using Alerton's VisualLogic graphical toolset. vlc 1600 datasheet

: Pulse inputs supported on inputs 1–15 (max 100 Hz frequency). The VLC-1600 is primarily used in central plant

: Features a 32-bit ARM Cortex-M4F (80 MHz) microprocessor with 512 MB of non-volatile flash memory. : Pulse inputs supported on inputs 1–15 (max

: Sixteen 16-bit high-resolution universal inputs that are auto-selectable for various signal types: Thermistor : 3k (Ibex) or 10k (Type II).

: Operates on 24 VAC @ 50–60 Hz, with a minimum draw of 5 VA.

: Integrates with intelligent wall sensors like the BACtalk Microset, Microset II, and Microset 4 on input 0 (IN-0) for local data display and setup.